KA2-EU

FOR EXTRACT AND EXHAUST AIR IN COMMERCIAL KITCHENS 

Rectangular fire damper for use in extract air and exhaust air ducts of commercial kitchens. For shutting off air ducts between two fire compartments

  • General building inspectorate licence Z-41.3.-716
  • Nominal sizes:
    • Width: 250 – 1200 mm in 25 mm increments
    • Height: 250 – 500 mm in 25 mm increments
    • Length: 580 mm – H = 400 mm; 680 mm – H = 500 mm
  • Large free cross-section ensures maximum safety
  • Low differential pressure and sound power level
  • Easy to clean thanks to smooth surfaces and an encased linkage
  • Can be integrated into the management and control equipment (MCE) with TROXNETCOM
  • Low-maintenance spring return actuator (1~ 230 V AC, 50 Hz, IP 54) with integrated control unit and connection casing
  • 2 thermoelectric release units with simple plug/socket mounting
  • Flow-independent design
  • No damper blade protrusion, no extension piece required
  • Short closing time of 3 s in the event of a fire
  • Approved for daily ventilation operation in accordance with DIN EN 15650 Annex C
  • EPD (Environmental Product Declaration)
  • Hygiene certificate according to VDI 6022
  • Based on fire damper FK2-EU (in accordance with DIN EN 15650)
  • Optional dry mortarless installation with installation kit ES for a wide range of installation situations

General information

Application

  • TROX fire dampers for shutting off extract air and exhaust air ducts of commercial kitchens, with general building inspectorate licence
  • Preventing the spread of fire and the transmission of smoke through air ducts into neighbouring fire compartments

Classification

  • Fire resistance class: Approval K90 (ve, ho), comparable to EI 90 ve, ho, i ↔ o) S according to DIN EN 13501

Variants

  • With installation kit ES

Nominal sizes
  • Width: 250 – 1200 mm in 25 mm increments
  • Height: 250 – 500 mm in 25 mm increments
  • Length: 580 mm – H = 400 mm; 680 mm – H = 500 mm

Attachments

  • 2 thermal release mechanisms
  • Z43KA Spring return actuator with integrated control unit and connection casing

Special characteristics
  • General building inspectorate licence Z-41.3.-716
  • Corresponds to DIN EN 15650:2010
  • Tested in accordance with DIN EN 1366-2 and the additional tests required by the DIBt
    • Essential components KA2-EU (at least casing and shut-off damper element): non-combustible building materials, at least class A2-s1, d0 according to DIN EN 13501-1
    • Building materials of the other components: at least E-d2 according to DIN EN 13501-1
  • Large free cross-section
  • Low differential pressure and sound power level
  • Integration into the MCE with TROXNETCOM

Parts and characteristics

  • Installation in horizontal and vertical air ducts
  • Installation orientation with any airflow direction
  • Large free cross-section, therefore low differential pressures
  • Reliable closing thanks to patented high-performance spring return actuator, even with existing deposits
  • Release temperature 72 °C

Construction features
  • Rigid rectangular casing, available in 25 mm increments
  • Based on the FK2-EU fire damper
  • Rectangular or square design, dimensionally stable frame, with perforated flange on both sides
  • Low-maintenance spring return actuator (1~ 230 V AC, 50 Hz, IP 54) with integrated control unit and connection casing
  • An extremely short closing time of 3 s minimises the risk of grease fires spreading in the event of a fire
  • Permitted for daily ventilation operation
  • 2 thermoelectric release units with simple plug/socket mounting
  • No damper blade protrusion, no extension piece required Flow-independent design
  • Design in accordance with product standard DIN EN 15650 and the specifications of the DIBt
  • Flat, metal-coated damper blade simplifies cleaning
  • Manual opening by crank handle possible
  • Remote monitoring and integration into an MCE via TROXNETCOM systems
  • Optional closing by means of a push button/wall switch by interrupting the supply voltage.
  • Integrated limit switches for Open and Closed position
  • Height and width available in 25 mm increments
  • Connecting flanges with fixing holes on both sides, suitable for air duct connection
  • Locking of the actuator in the event of a fire to prevent accidental opening
  • Signalling of operating states via the LED on the actuator
  • Installation with mortar or with dry mortarless installation kit

Material and surfaces
  • Casing: galvanised sheet steel or optionally stainless steel 1.4301
  • Damper blade made of special insulating material, metalcoated, or optionally made of stainless steel 1.4301
  • Damper blade shaft: stainless steel 1.4301

Installation and commissioning
Install the fire damper according to the operating and installation manual.
Mortar-based installation in walls:
  • In solid wall
  • In plastered solid wall
  • In gypsum wallboards
  • In lightweight partition wall/fire wall with metal studs and cladding on both sides
  • In lightweight partition wall with metal stud
  • In lightweight partition wall with timber stud/half-timbered construction
  • In shaft wall with metal stud
Dry mortarless installation with KA2-EU installation kit ES in walls:
  • Below a flexible ceiling joint
  • In lightweight partition wall with metal stud
  • In lightweight partition wall with timber stud/half-timbered construction
  • In shaft wall with metal stud

Mortar-based installation into solid ceilings

  • Mortar-based installation into solid ceilings
  • Mortar-based installation into solid ceilings with concrete base

Standards, guidelines and certificates

  • Tested for fire resistance properties in accordance with DIN EN 1366-2 and the additional tests and requirements stipulated by the DIBt
  • Proven as a multi-purpose actuator in accordance with DIN EN 15650 Annex C, approved for daily ventilation operation
  • General building inspectorate licence Z-41.3.-716

  • Hygiene certificate according to VDI 6022
  • EPD (Environmental Product Declaration) in accordance with DIN EN ISO 14025 and DIN EN 15804
  • Proven corrosion protection according to DIN EN 15650 in connection with DIN EN 60068-2-52

Maintenance

  • At the initiative of the owner of the ventilation system, the function of the fire damper must be checked at least every six months in accordance with the specifications of VDI 2052, taking into account the basic maintenance measures in accordance with DIN EN 13306 in conjunction with DIN 31051. If two consecutive tests at intervals of 6 months do not reveal any functional defects, the fire damper only needs to be checked once a year.
  • In general, closing and reopening is sufficient, with spring return actuator also remotely operated or by means of a voltage interruption
  • Fire dampers must be included in the regular cleaning schedule for the ventilation and air conditioning system. For details on maintenance and inspection, please refer to the installation and operating manual

Informaţii tehnice

  • FUNCTION
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE
Schematische Darstellung KA2-EU

1 KA2-EU
2 Spring return actuator with integrated limit switches
3 Thermal release unit
4 Connection casing
5 Crank handle
6 Position indicator

Functional description

Type KA2-EU fire dampers close off extract air and exhaust air ducts in commercial kitchens and prevent the spread of fire and smoke via air ducts into adjacent fire compartments. In standard operation, the fire damper is in the Open position. This is made possible by the electrically operated spring return actuator, which enables the motorised opening of fire damper. The spring return actuator also enables the fire damper to be activated by the management and control equipment (MCE) during maintenance work and functional checks. In the event of a fire, one of the two thermoelectric release units is triggered. From a trigger temperature of 72 °C, the damper blade closes the fire damper within 3 seconds. In addition, an interruption in the supply voltage also causes the fire damper to close. The closing process is based on the fail-safe principle. The control system of the spring return actuator differentiates between a fire and other interruptions. The limit switch signal can also be used to close other KA2-EU units. The signal on leaving the Open end position can be used to switch off the supply voltage to other fire dampers. Fire dampers that are further away from the fire then close within 10 seconds. TROXNETCOM offers further solutions. Limit switches can be used for position indication. When leaving the Open position, the signal from the Open limit switch must be used to switch off the fan.

Nominal sizes

250 × 250 to 1200 × 500 mm

Volume flow rate range

up to 4500 l/s or 16200 m³/h

Operating temperature

10 – 50 °C

Release temperature

72 °C

Maximum upstream velocity

≤ 7.5 m/s

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.


Specification text

Fire dampers with a general building inspectorate licence and a fire resistance duration of 90 min for shutting off extract and exhaust air ducts in commercial kitchens in the event of a fire. Reliable closing thanks to the low-maintenance spring return actuator, even with existing deposits. Tested for fire resistance properties in accordance with DIN EN 1366-2. Airtight casing, tightness class B in accordance with DIN EN 1751, made of galvanised sheet steel, optionally made of stainless steel; flowindependent design. Shut-off damper blade made of special insulating material, metal-coated, airtight closing. With 2 compact thermal release mechanisms 72 °C, 2 electrical limit switches to indicate damper position CLOSED or OPEN, fan switch-off and integration into the MCE. Control unit and connection casing with plug/socket connection integrated in the spring return actuator. Designed for 10000 cycles and a closing time of 3 s in the event of fire and 10 s in ventilation mode. Suitable for mortar-based and dry mortarless installation in solid walls or ceilings, shaft walls with metal studs, lightweight partition walls with metal or wooden studs and connection to horizontal and vertical air ducts with a connecting flange.


Classification

  • Fire resistance class: Approval K90 (ve, ho), comparable to EI 90 (ve, ho, i ↔ o) S according to DIN EN 13501

Material and surfaces
  • Casing: galvanised sheet steel or optionally stainless steel 1.4301
  • Damper blade made of special insulating material, metalcoated, or optionally made of stainless steel 1.4301
  • Damper blade shaft: stainless steel 1.4301

Technical data
  • Nominal sizes: 250 × 250 – 1200 × 500 mm
  • Volume flow range: 16200 m³/h
  • Operating temperature: 10 – 50 °C
  • Release temperature: 72 °C
  • Maximum upstream velocity: ≤ 7.5 m/s

Standards, guidelines and certificates
  • Tested for fire resistance properties in accordance with DIN EN 1366-2 and the additional tests and requirements stipulated by the DIBt
  • Proven as a multi-purpose actuator in accordance with DIN EN 15650 Annex C, approved for daily ventilation operation
  • General building inspectorate licence Z-41.3.-716
  • Hygiene certificate according to VDI 6022
  • EPD (Environmental Product Declaration) in accordance with DIN EN ISO 14025 and DIN EN 15804
  • Proven corrosion protection according to DIN EN 15650 in connection with DIN EN 60068-2-52

Nominal sizes
  • Width: 250 – 1200 mm in 25 mm increments
  • Height: 250 – 500 mm in 25 mm increments
  • Length: 580 mm – H = 400 mm; 680 mm – H = 500 mm

Attachments

  • 2 thermal release mechanisms
  • Z43KA Spring return actuator with integrated control unit and connection casing

Zubehör

  • Dry mortarless installation kit

Equivalence criteria
  • Free cross-section at least 70 % of the nominal size
  • Smooth inner surfaces without grooves to prevent deposits
  • Low-maintenance spring return actuator with integrated control unit and connection casing
  • Independent of air direction - air flow in both directions without extension piece with flow guide device
  • 10,000 cycles in accordance with DIN EN 15650, Annex C 3.2, approved for daily ventilation operation
  • CE marking in accordance with the EC Declaration of Conformity, within the meaning of the Machinery Directive 2006/42 EC as a complete machine

Manufacturer

TROX SE

Type: KA2-EU


KA2-EU2/DE/500 × 500 × 680/ES/Z43KA









||||||




123456





1 Type

KA2-EU Fire damper for the extract air of commercial kitchens

2 Construction

No entry: standard construction

2 Stainless steel casing

3 Country of destination

Specify country code

4 Nominal size [mm]

Specify width × height × length

5 Accessories

No entry: without accessories

ES Installation kit for dry mortarless installation

6 Attachment

Z43KA Spring return actuator 230 V

Order example: KA2-EU-2/DE/500×500×680/ES/Z43KA


TypeKA2-EU – Fire damper for the extract air of commercial kitchens
ConstructionStainless steel casing
Country of destination Germany
Nominal size [mm]Width 500, height 500, length 680
AccessoriesInstallation kit for dry mortarless installation
AttachmentSpring return actuator 230 V

Descărcări fişiere

informaţii produs

certificate

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"1; mode=block", "x-content-type-options"=>"nosniff", "x-download-options"=>"noopen", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8"}

Distribuie pagina

Recomandaţi această pagină

Recomandaţi această pagină prin trimiterea unui link prin mail.

Câmpurile marcate cu (*) sunt obligatorii.

Distribuie pagina

Vă mulţumim pentru recomandare!

Recomandarea dumneavoastră a fost expediată şi va fi primită în curând.


Contact

Suntem aici pentru dumneavoastră

Vă rugăm să exprimaţi mesajul dumneavoastră şi tipul de cerere
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040

Câmpurile marcate cu (*) sunt obligatorii.

Contact

Vă mulţumim pentru mesaj!

Mesajul dumneavoastră este trimis şi va fi procesat în curând.
Departamentul nostru de Cereri Service o să vă contacteze în cel mai scurt timp Pentru întrebări generale privind produsele sau serviciile puteţi suna şi la:
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040

Contact

Suntem aici pentru dumneavoastră

Vă rugăm să exprimaţi mesajul dumneavoastră şi tipul de cerere
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040

Attachment (max. 10MB)

Câmpurile marcate cu (*) sunt obligatorii.

Contact

Vă mulţumim pentru mesaj!

Mesajul dumneavoastră este trimis şi va fi procesat în curând.
Departamentul nostru de Cereri Service o să vă contacteze în cel mai scurt timp Pentru întrebări generale privind produsele sau serviciile puteţi suna şi la:
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040