Nominal sizes
Useful additions
Maintenance
1 Integrated attenuator
2 Differential pressure sensor
3 Control components, e.g. Easy controller
4 Damper blade with seal
Nominal sizes | 125 – 315 |
Volume flow rate range | 30 – 840 l/s or 108 – 3024 m³ /h |
Volume flow rate control range (unit with dynamic differential pressure measurement) | Approx. 10 to 100 % of the nominal volume flow rate |
Minimum differential pressure | 5 – 65 Pa |
Maximum differential pressure | 1000 Pa |
Operating temperature | 10 – 50 °C |
Nominal sizes | 125 – 315 |
Volume flow rate range | 27 – 1093 l/s or 95 – 3937 m³/h |
Volume flow rate control range (unit with dynamic differential pressure measurement) | Approx. 10 – 100 % of the nominal volume flow rate |
Minimum differential pressure | Up to 106 Pa (without secondary silencer) |
Maximum differential pressure | 1000 Pa |
Operating temperature | 10 to 50 °C |
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Specification text
Rectangular VAV terminal units for variable and constant volume flow systems, for demanding acoustic requirements, for supply air, available in 5 nominal sizes. High control accuracy of the set volume flows under any upstream conditions. Ready-tocommission control unit, consisting of mechanical parts and electronic control components. Each unit contains an averaging differential pressure sensor for volume flow measurement, a damper blade, and an integrated sound attenuator. Control components are factory-mounted, tubed and wired. Differential pressure sensor with 3 mm measuring holes, making it insensitive to contamination. Casing with acoustic and thermal insulation. Position of the damper blade visible from the outside due to the shape of the shaft. The damper blade is factory-set to open position, which allows airflow even without control function; except for variants with defined NC safety position. Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.
Special features
Connection type
Sizing data
| TZ-Silenzio | – | D | / | 200 | / | Easy |
| | | | | | | | | |||
| 1 | 2 | 3 | 4 |
1 Type
TZ-Silenzio VAV terminal unit, supply air
2 Acoustic cladding
No entry: none
D with acoustic cladding
3 Nominal size
125, 160, 200, 250, 315
4 Attachments (control component)
Easy Volume flow controller, dynamic, analogue interface, setting of qᵥmin and qᵥmax with potentiometers (provided on site)
Order example: TZ–Silenzio/125/Easy
| Acoustic cladding | None |
| Nominal size | 125 |
| Attachments (control component) | Easy volume flow controller, dynamic, setting of qᵥmin and qᵥmax with potentiometers |
Distribuie pagina
Recomandaţi această pagină
Recomandaţi această pagină prin trimiterea unui link prin mail.
Distribuie pagina
Vă mulţumim pentru recomandare!
Recomandarea dumneavoastră a fost expediată şi va fi primită în curând.
Contact
Suntem aici pentru dumneavoastră
Vă rugăm să exprimaţi mesajul dumneavoastră şi tipul de cerere
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040
Contact
Vă mulţumim pentru mesaj!
Mesajul dumneavoastră este trimis şi va fi procesat în curând.
Departamentul nostru de Cereri Service o să vă contacteze în cel mai scurt timp Pentru întrebări generale privind produsele sau serviciile puteţi suna şi la:
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040
Contact
Suntem aici pentru dumneavoastră
Vă rugăm să exprimaţi mesajul dumneavoastră şi tipul de cerere
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040
Contact
Vă mulţumim pentru mesaj!
Mesajul dumneavoastră este trimis şi va fi procesat în curând.
Departamentul nostru de Cereri Service o să vă contacteze în cel mai scurt timp Pentru întrebări generale privind produsele sau serviciile puteţi suna şi la:
Tel.: +40 31 82 43 041 | Fax: +40 31 82 43 040